The ANDSTF air velocity and temperature transmitter is actually a combined sensor for air flow and temperature for duct application. It is based on a microcontroller for measuring nonaggressive gaseous flows in the range of 0 to 20 m/s. Available with both 0-10 V and 4-20 mA output. In addition, this sensor can be delivered with an replay output and a display integrated in the case for displaying real-time values.
Product number
Product number: ANDSTF/X/X
Technical Specifications
| Power supply: | 20…30 V AC/DC |
| Connection: | 3 wired connection |
| Connection clamp: | Screw clamps, max 1.5 mm² |
| Switching output: | Relay 24 V / 1A, potential free changer (optional) |
| Relay- Thresholds: | 25% / 50% / 75% / 100% |
| Power consumption – I (4-20mA): | max. 70 mA |
| Power consumption – U (0-10V): | max. 25 mA |
| Sensor setup duration: | 10 min (before ready to use) |
| Mounting equipment (included): | Mounting flange |
| Output signal | |
| Output signal – I (4-20mA): | 4…20 mA – 3 wired – for air flow (m/s) and temperature (°C) |
| Analogue output burden: | 50…500 Ohm |
| Output signal – U (0-10V): | 0…10 V – 3 wired – for air flow (m/s) and temperature (°C) |
| Analogue output load: | 10…100 kOhm |
| Air Flow – Air Velocity | |
| Measuring range Air Flow (velocity ranges) | 0…2 m/s 0…10 m/s 0…20 m/s |
| Tolerance Air Flow | 0…2 m/s < 0,2 m/s (20°C) ± 5% from reading 0…10 m/s < 0,5m/s (20°C) ± 5% from reading 0…20 m/s < 1 m/s (20C) ± 5% from reading |
| Measuring range Temperature | 4 presets – adjustable presetted ranges: 0 … 50 °C -10 … 50 °C 0 … 100 °C -20 … 80 °C |
| Tolerance Temperature | ± 0.3 °K (5…60 °C) + 1.5% f.s.(Velocity > 0.5 m/S) |
| Casing | |
| Dimensions | 75x69x44 mm |
| Material | PA6, similar RAL 9010 |
| Cable inlet | M16x1.5 for wire diameter 4…10 mm |
| Environmental conditions | 0…50 °C; 0…98% r.h. |
| Protection sleeve | 12×195 mm, perforiert |
| Sensor protection | Stainless steel |
| Protection class | IP65 |
Electrical connections
| Pin – Electrical Connection | Type U (0…10 V) | Type I (4…20 mA) |
| 1 | temperature | – |
| 2 | air velocity | – |
| 3 | – | temperature |
| 4 | – | air velocity |
| 7 | V+ | |
| 8 | GND | |
| 9 | relay NC (optional) | |
| 10 | relay C (optional) | |
| 11 | relay NO (optional) | |
| 12 | – | |
| 13 | – | |

Explore our range of Flow Sensors or contact us for more information, here you can learn more about Air Stream Monitor ANDSTF1 .
Datasheet ANDSTF/[X]/[X]
Versions of ANDSTF/[X]/[X]
| Product Code | Output Air Flow (m/s) | Output (°C) | Output relay | Display |
| STF/R-U/S | 0…10 V | 0…10 V | ||
| STF/R-U/S/R | 0…10 V | 0…10 V | Yes | |
| STF/R-U/S-D | 0…10 V | 0…10 V | Yes | |
| STF/R-U/S/R-D | 0…10 V | 0…10 V | Yes | Yes |
| STF/R-I/S | 4…20 mA | 4…20 mA | ||
| STF/R-I/S/R | 4…20 mA | 4…20 mA | Yes | |
| STF/R-I/S-D | 4…20 mA | 4…20 mA | Yes | |
| STF/R-I/S/R-D | 4…20 mA | 4…20 mA | Yes | Yes |