Outdoor Temperature Sensor with Sun Protection ANDAUTFEXT2 passive sensor is used for temperature measurements in outdoor areas. Radiant heat is diverted via the integrated feeler tube, protecting the device from insolation and thus allowing for a more accurate measurement. With the help of the respective sensors (see below), the device can be connected to all conventional control and display systems.
Additional options for sensor ANDAUTFEXT2 (surcharges):
- 3 wire connection,
- 4 wire connection.
Sensor type:
- Passive sensor
Alternative sensor versions:
- Active Outdoor Temperature Sensor with Sun Protection ANDAUTFEXT2/MU,
- Modbus Outdoor Temperature Sensor with Sun Protection ANDAUTFEXT2/MD.
Product number – Outdoor Temperature Sensor with Sun Protection
Product number: ANDAUTFEXT2
Technical Specifications – Outdoor Temperature Sensor with Sun Protection
Measuring range: | -50 °C … +100 °C |
Tmax. (housing): | 100°C |
Sensor: | according to customer request (see table) |
Switching mode: | 2-wire connection (standard) |
Connection: | Screw clamps, max 1.5 mm² |
Housing: | PA6 15% GK, Colour RAL 9011 |
Housing dimensions: | 75 x 69 x 44 mm |
Sun protection (Sleeve): | 10 x 42 mm |
Protection class: | IP65 |
Mounting equipment (included): | Screws and dowels |
PRODUCT ENQUIRY
Looking for a larger quantity? Do you need a variety of the product offered? Send us your custom enquiry.
Versions of ANDAUTFEXT2
Sensor type | ANDAUTFEXT2 |
Pt100 | ANDAUTFEXT2/Pt100 |
Pt100 1/3DIN | ANDAUTFEXT2/Pt100 1/3DIN |
Pt1000 | ANDAUTFEXT2/Pt1000 |
Pt1000 1/3DIN | ANDAUTFEXT2/Pt1000 1/3DIN |
Ni1000 | ANDAUTFEXT2/Ni1000 |
Ni1000TK5000 | ANDAUTFEXT2/Ni1000TK5000 |
NTC 5k, 10k, 20k, Precon, KTY81-210 | ANDAUTFEXT2/… |
NTC 1,8kOhm | ANDAUTFEXT2/NTC1,8k |
LM235Z | ANDAUTFEXT2/LM235Z |
DS18B20 | ANDAUTFEXT2/DS18B20 |
How to order?
Order example: ANDAUTFEXT2 Sensor with Pt1000 sensor = ANDAUTFEXT2 / PT1000