Indoor Air Quality Sensor Flush Mounted ANDRALQ-UP sensor is equipped with a 0-10 V/DC output signal and is available for up to 3 measuring categories (only available as a VOC sensor for the moment). The VOC can be combined with the following switch series: GIRA E2, Event / Merten System M / Jung A500, Ap581, AS500 / Berker B.1, B.7.
Product number
Product number: ANDRALQ-UP
Technical Specifications
Sensor system | |
VOC Sensor: | Metal oxide sensor with a semi-automatic calibration |
Fields of application: | Indoors 0°C…+50°C, 5..95% r.h. (without sewing) |
Measuring range: | 450-2000 ppm CO2 equivalent |
Electronics | |
Supply voltage: | 12…25 VAC or 12…25 VDC |
Power consumption: | 14 mA at 24 VDC |
Signal output: | 0-10 V/DC (standard) |
Warm-up phase: | 15 min after current contact |
Dimensions | |
Casing (W x H): | 55 x 55 mm |
Casing depth: | ca. 10 mm |
Wall mounting: | receptacle provided by customer, Ø 60 mm, with steel mounting plate |
Connections: | Plug with screw clamps for 0.25-1.5 mm2 (cable/strand) |
Casing: | Plastic (partially painted): Pure white, gloss (similar to RAL 9010) matt, or special colors |
QUICK ENQUIRY
Skip the waiting line with quick enquiry.
Datasheet ANDRALQ-UP
Versions of ANDRALQ-UP
Type | Output |
ANDRALQ-UP | 0-10V |