Surface Temperature Sensor ANDOBTF/MU active sensor is designed for measuring the temperature on plain surfaces such as windows. The feeler is made of aluminum and can be mounted to the respective surface with the borehole (4,1 mm) located on the upper half of the sensor. The sensors are equipped with a standardized 0…10 V or 4…20mA output and can be connected to any PLC or DDC.
Additional options for sensor ANDOBTF/MU (surcharges):
- display,
- power supply cord per meter (PVC),
- relay.
Sensor type:
- Active sensor
Alternative sensor versions:
- Passive Surface Temperature Sensor ANDOBTF,
- Modbus Surface Temperature Sensor ANDOBTF/MD.
Product number
Product number: ANDOBTF/MU
Technical Specifications
Measuring transducer | |
Required temperature sensor: | Pt1000 class B (2-wire) |
Power supply: | 12-34 V AC/V DC with 4-20 mA |
12-34 V AC/V DC with 0-10 V | |
Analog output burden (4…20 mA): | 50-500 Ohm |
Analog output burden (0…10 V): | 10-100 kOhm |
Power input with 0…10 V: | 20 mA |
Power input with 4…20 mA: | 24-44 mA |
Accuracy: | ±0,2K + max. 3 % full scale |
Measuring range: | 24 measuring ranges available |
Operating temperature: | -30 °C … +70 °C |
Connection: | 3-wire (2-wire optional with 4-20 mA) |
Norms: | CE, Electromagnetic Compatibility acc. EN 61326-1 2013, EG Act 2004/108/EG |
Temperature Sensor | |
Measuring range: | -35 °C … +105 °C |
Temperature sensor: | Pt1000 class B (2-wire) |
Connection: | Screw clamps, max 1.5 mm² |
Protection sleeve: | 8 x 8 x 40 mm, Aluminium |
Tmax. (housing): | +100 °C |
Housing: | PA6 15% GK, Colour RAL 9011 |
Measurements Housing: | 75 x 69 x 44 mm |
Protection class: | IP54 |
PRODUCT ENQUIRY
Looking for a larger quantity? Do you need a variety of the product offered? Send us your custom enquiry.
Versions of ANDOBTF/MU
Type | Output | Cable length |
ANDOBTF/MUV | 0…10 V | 2m |
ANDOBTF/MUA | 4…20mA | 2m |
How to order?
Order example: ANDOBTF/MU sensor with 0-10 V output signal = ANDOBTF / MUV